Temperature measurement faults are often due to wiring issues, poor installation, or sensor degradation rather than sensor failure itself. Effective troubleshooting requires a systematic approach—starting with simple checks and moving toward calibration and instrumentation.
The most common source of error in temperature measurement is the sensor not accurately reflecting the temperature of its environment. This can be due to:
- Poor thermal contact — between the sensor and the medium, or between the sensor and its housing (probe, sheath, or thermowell).
- Sensor degradation — resulting in drift from its original calibration.
- Wiring faults — which are more common than sensor or instrument failures.
- Instrument calibration errors — which can mimic sensor faults.
- Start with Wiring
Faulty wiring and poor connections often cause more issues than the sensors themselves. Always inspect wiring first. Ensure connections are tight, free of corrosion, and follow the correct wiring scheme.
- Check Thermal Contact
Poor installation can prevent the sensor from properly sensing the medium. If installation guidelines were followed, many of these issues should be avoided. Visually inspect for:
- Clean and intact contact areas
- Secure mechanical junctions
- Adequate insertion depth and positioning in the process
Poor contact, especially in closed control loops, can cause lag, error, and unstable process control.
- Look for Sensor Degradation
Sensor drift typically happens over time and differs between sensor types:
- Thermocouples: May suffer from poor insulation, thermoelectric inhomogeneity, or junction deterioration.
- RTDs: Prone to internal lead issues, mechanical shock, chemical poisoning, or lead wire imbalance.
Use calibration checks and diagnostics to confirm degradation.
- Perform Quick Tests
- Thermocouple: Disconnect sensor and short input terminals. If ambient temperature displays, the sensor is at fault.
- RTD: Disconnect sensor and connect a 100 Ω resistor. If 0°C displays, the sensor is faulty.
Measure resistance:
- Low resistance: May indicate shorts or wiring faults.
- High resistance: Could suggest thinning wires (thermocouples) or open circuits.
Be alert to:
- Reversed polarity: Leads to downscale readings or large errors (up to 100°C).
- Wrong cable type or thermocouple type: Can also cause significant error.
- Recognize Common Indicators
Symptom Possible Cause Full-scale high reading Open circuit, loose wire, sensor failure Persistent low reading Wrong thermocouple/cable type, short circuit Gradual drift Sensor aging or degradation Intermittent fluctuations Loose wiring, poor joints, EMI/noise pickup High RTD reading High circuit resistance, excessive current, self-heating Low RTD reading Insulation leakage, lead shorts - Polarity and Cable Checks
Thermocouples are particularly sensitive to connection polarity and cable alloys. Reversed polarity or mismatched extension cables can cause major errors. Always check:
- Cable color codes and type
- Correct polarity (positive to positive)
- That all connections are secure and follow isothermal practices
- Consider Instrumentation and Environment
- Inspect isolators, transmitters, multiplexers, and receiving instruments.
- Use portable calibrators and simulators for diagnostics.
- Confirm cold junction compensation is functioning correctly in thermocouple systems.
If the sensor and wiring are sound, turn to the rest of the system:
Summary
Sensor faults are rarely the root cause of measurement errors. Start with wiring and connection checks, then look at thermal contact and sensor degradation. Use resistance measurements and simulation tools to identify open or short circuits, reversed polarity, or incorrect cable types. Thermocouples are more prone to drift and wiring sensitivity, while RTDs are typically stable but affected by insulation leakage or self-heating. Systematic diagnostics and good installation practices are key to reliable operation.
Note: The information in this guide is provided for general informational and educational purposes only. While we aim for accuracy, all data, examples, and recommendations are provided “as is” without warranty of any kind. Standards, specifications, and best practices may change over time, so always confirm current requirements before use.
Need help or have a question? We’re here to assist — feel free to contact us.